Contactors MinicontactorsMC09.10 220..240V / 40..450Hz contactor

MC09.10 220..240V / 40..450Hz contactor

EAN: 8590206782067
Order number: GJL1211001R9065
Power: 4.0 kW
Control voltage: 220-240
Control frequency: 40-450
Impulse withstand voltage [kW] 6
Main circuit
No. of main contacts NO 3
No. of main contacts NC 0
Rated insulation voltage Ui [V] 690
Conventional free thermal current [A] 20
Rated operational current Ie in AC-1 / 220..230V [A] 20
Rated operational current Ie in AC-1 / 380..400V [A] 16
Rated operational current Ie in AC-1 / 500V [A] 12
Rated operational current Ie in AC-1 / 660..690V [A] 6
Rated operational current Ie inAC-3 400V [A] 9
Rated operational current Ie inAC-4 380..400V [A] 9
Rated operational current Ie in AC-3 500V [A] 5,5
Rated operational current Ie in DC-1 220V [A] 14
Rated operational current Ie in DC-3 220V [A] 4
Rated operational current Ie in DC-5 220V [A] 2
Max. output power of controlled motor in AC-3 380..400V [kW] 4
Max. number of on-load op. cycles at max. load in AC- 1 [op. cyc./hour] 300
Max. number of on-load op. cycles at max. load in AC- 3 [op. cyc./hour] 600
Electrical durability in AC-1 at 380-400V [op. cycles] 150000
Electrical durability in AC-3 at 380-400V [op. cycles] 1500000
Recommended fuse char. aM [A] / Type of co-ordination with SCPD 20 / 2
Mechanical durability [op. cycles] 10 x 106
Max. cross section of copper wire [mm2] rigid / flexible 2 x 1-2,5 / 2 x 0,75-2,5
Auxiliary circuits
No. of aux. contacts NO 1
No. of aux. contacts NC 0
Rated insulation voltage Ui [V] 690
Conventional free thermal current [A] 6
Rated operational current Ie in AC-15 / 220..230V [A] 4
Rated operational current Ie in AC-15 / 380..400V [A] 3
Rated operational current Ie in AC-15 / 500V [A] 2
Rated operational current Ie in DC-14 / 24V [A] 2,5
Rated operational current Ie in DC-14 / 125V [A] 0,7
Rated operational current Ie in DC-14 / 250V [A] 0,4
Recommended fuse char. gG [A] , type of co-ordination 2 10
Max. number of on-load op. cycles at max. load in AC- 1 [op. cyc./hour] 600
Mechanical durability [op. cycles] 10000000
Max. cross section of copper wire [mm2] rigid / flexible 2 x 1-2,5 / 2 x 0,75-2,5
Control circuits
Control voltage [V] 220-240
Control frequenci [Hz] 40-450
Hold-in input power [VA;W] 3,5
Other data
Width [mm] 47,5
High [mm] 57,5
Depth [mm] 46,5
Mass [kg] 0,18
Degree of protection IP20
Image 1 Image 2