Home
Products
Selection Guide
Download
Company history
Contact
Contactors – Overload protection relays – Timing relays – Motor starters – Rotary CAM switches
tel.: +420 261 106 111
e-mail:
epm@epm.cz
Catalogue
Contactors
Contactors up to 150A series "C"
accessories for contactors series "C"
Compact contactors up to 250A series "VF" and "RM"
Auxiliary contators
Capacitor contactors
Contactors for heavy duty
Contactors for household applications
Contactors for middle-frequency currents
Minicontactors
Vacuum contactors
Motor starters
Overload protection relays
Timing relays
Cam switches
Accessories and equipment
Download
view documents
close
Produkt:
Name and surname:
E-Mail:
Přijmení:
Telephone no.:
Question:
Contactors
Contactors up to 150A series "C"
C23.10 48V / 50Hz 3-pole contactor
C23.10 48V / 50Hz 3-pole contactor
EAN:
8590206137058
Order number:
111161805000
Power:
11.0 kW
Control voltage:
48
Control frequency:
50
Download PDF
Product inquiry
Technical parameters
Blueprints
Related products
Impulse withstand voltage [kW]
8
Main circuit
No. of main contacts NO
3
No. of main contacts NC
0
Rated insulation voltage Ui [V]
690
Conventional free thermal current [A]
25
Rated operational current Ie in AC-1 / 380..400V [A]
25
Rated operational current Ie inAC-3 400V [A]
23
Rated operational current Ie inAC-4 380..400V [A]
8
Rated operational current Ie in DC-1 220V [A]
25
Rated operational current Ie in DC-3 220V [A]
12
Rated operational current Ie in DC-5 220V [A]
8
Max. output power of controlled motor in AC-3 220..230V [kW]
5,5
Max. output power of controlled motor in AC-3 380..400V [kW]
11
Max. output power of controlled motor in AC-3 500V [kW]
11
Max. output power of controlled motor in AC-3 660..690V [kW]
9
Max. output power of controlled motor in AC-4 400V [kW]
3,7
Max. output power of controlled motor in AC-4 500V [kW]
3,7
Recommended fuse char. aM [A] / Type of co-ordination with SCPD
25 / 2
Max. cross section of copper wire [mm2] rigid / flexible
1-4 / 1-2,5
Auxiliary circuits
No. of aux. contacts NO
1
No. of aux. contacts NC
0
Rated insulation voltage Ui [V]
690
Rated operational current Ie in AC-15 / 220..230V [A]
4
Rated operational current Ie in AC-15 / 380..400V [A]
2
Max. cross section of copper wire [mm2] rigid / flexible
1-4
Control circuits
Control voltage [V]
48
Control frequenci [Hz]
50
Pull-in input power [VA;W]
60
Hold-in input power [VA;W]
10,5 / 3,9
Other data
Width [mm]
45
High [mm]
78,5
Depth [mm]
73
Mass [kg]
0,31
Degree of protection
IP20