Home
Products
Selection Guide
Download
Company history
Contact
Contactors – Overload protection relays – Timing relays – Motor starters – Rotary CAM switches
tel.: +420 261 106 111
e-mail:
epm@epm.cz
Catalogue
Contactors
Contactors up to 150A series "C"
accessories for contactors series "C"
Compact contactors up to 250A series "VF" and "RM"
Auxiliary contators
Capacitor contactors
Contactors for heavy duty
Contactors for household applications
Contactors for middle-frequency currents
Minicontactors
Vacuum contactors
Motor starters
Overload protection relays
Timing relays
Cam switches
Accessories and equipment
Download
view documents
close
Produkt:
Name and surname:
E-Mail:
Přijmení:
Telephone no.:
Question:
Contactors
Contactors up to 150A series "C"
C115.21 220-230V / 50Hz 3-pole contactor
C115.21 220-230V / 50Hz 3-pole contactor
EAN:
8590206226677
Order number:
111280867340
Power:
55.0 kW
Control voltage:
220-230
Control frequency:
50
Download PDF
Product inquiry
Technical parameters
Blueprints
Related products
Impulse withstand voltage [kW]
8
Main circuit
No. of main contacts NO
3
No. of main contacts NC
0
Rated insulation voltage Ui [V]
690
Conventional free thermal current [A]
160
Rated operational current Ie in AC-1 / 380..400V [A]
110
Rated operational current Ie inAC-3 400V [A]
115
Rated operational current Ie in DC-1 220V [A]
115
Rated operational current Ie in DC-3 220V [A]
63
Rated operational current Ie in DC-5 220V [A]
40
Max. output power of controlled motor in AC-3 220..230V [kW]
30
Max. output power of controlled motor in AC-3 380..400V [kW]
55
Max. output power of controlled motor in AC-3 500V [kW]
55
Max. output power of controlled motor in AC-3 660..690V [kW]
45
Max. output power of controlled motor in AC-4 400V [kW]
18,5
Recommended fuse char. aM [A] / Type of co-ordination with SCPD
125 / 2
Mechanical durability [op. cycles]
1 x 106
Max. cross section of copper wire [mm2] rigid / flexible
6-50 / 6-50
Auxiliary circuits
No. of aux. contacts NO
2
No. of aux. contacts NC
1
Rated insulation voltage Ui [V]
690
Conventional free thermal current [A]
12
Rated operational current Ie in AC-15 / 220..230V [A]
4
Rated operational current Ie in AC-15 / 380..400V [A]
2
Max. cross section of copper wire [mm2] rigid / flexible
1-2,5 / 0,75-1,5
Control circuits
Control voltage [V]
220-230
Control frequenci [Hz]
50
Hold-in input power [VA;W]
30 / 6,5
Other data
Width [mm]
70
High [mm]
107
Depth [mm]
116
Mass [kg]
1,668
Degree of protection
IP20